Frequency Setting By External Terminals; Operation By Multi-Speed Operation (Pr. 4 To Pr. 6, Pr. 24 To Pr. 27, Pr. 232 To Pr. 239) - Mitsubishi Electric FR-E720-0.1 K Instruction Manual

Table of Contents

Advertisement

Frequency setting by external terminals

4.7

Frequency setting by external terminals

Purpose
Make frequency setting by
combination of terminals
Perform jog operation
Infinitely variable speed setting by
terminals
4.7.1

Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)

Can be used to change the preset speed in the parameter with the contact signals.
Any speed can be selected by merely turning ON/OFF the contact signals (RH, RM, RL, REX signals).
Parameter
Number
Multi-speed setting (high
4
speed)
Multi-speed setting (middle
5
speed)
Multi-speed setting (low
6
speed)
24 ∗
Multi-speed setting (speed 4)
25 ∗
Multi-speed setting (speed 5)
26 ∗
Multi-speed setting (speed 6)
27 ∗
Multi-speed setting (speed 7)
232 ∗
Multi-speed setting (speed 8)
233 ∗
Multi-speed setting (speed 9)
234 ∗
Multi-speed setting (speed 10)
235 ∗
Multi-speed setting (speed 11)
236 ∗
Multi-speed setting (speed 12)
237 ∗
Multi-speed setting (speed 13)
238 ∗
Multi-speed setting (speed 14)
239 ∗
Multi-speed setting (speed 15)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
* The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 183)
Speed 1
(High speed)
Speed 2
(Middle speed)
ON
RH
ON
RM
RL
REMARKS
For multi-speed setting, if two or three speeds are simultaneously selected, priority is given to the set frequency of the lower
signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.
The RH, RM, RL signals are assigned to the terminal RH, RM, RL in the initial setting. By setting "0 (RL)", "1 (RM)", "2 (RH)" in
any of Pr. 178 to Pr. 184 (input terminal function selection), you can assign the signals to other terminals.
98
Multi-speed operation
Jog operation
Remote setting function
Name
Initial Value
(1)
The inverter operates at frequencies set in Pr. 4 when RH signal is ON,
Pr. 5 when RM signal is ON and Pr. 6 when RL signal is ON.
Speed 3
(Low speed)
Time
ON
Parameter that should be Set
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Setting Range
60Hz
0 to 400Hz
30Hz
0 to 400Hz
10Hz
0 to 400Hz
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
3-speed setting (Pr. 4 to Pr. 6)
Pr. 15, Pr. 16
Pr. 59
Description
Frequency when RH turns ON
Frequency when RM turns ON
Frequency when RL turns ON
Frequency from 4 speed to 15 speed can
be set according to the combination of
the RH, RM, RL and REX signals.
9999: not selected
Refer to Page
98
100
102

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents