Frequency Setting By External Terminals; Operation By Multi-Speed Operation (Pr. 4 To Pr. 6, Pr. 24 To Pr. 27, Pr. 232 To Pr. 239) - Mitsubishi Electric FR-E720-600 Instruction Manual

Hide thumbs Also See for FR-E720-600:
Table of Contents

Advertisement

4.7

Frequency setting by external terminals

Purpose
Make frequency setting by
combination of terminals
Perform jog operation
Infinitely variable speed setting by
terminals
4.7.1

Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)

Can be used to change the preset speed in the parameter with the contact signals.
Any speed can be selected by merely turning on-off the contact signals (RH, RM, RL, REX signals).
Parameter
Number
Multi-speed setting (high
4
speed)
Multi-speed setting (middle
5
speed)
Multi-speed setting (low
6
speed)
24 ∗
Multi-speed setting (speed 4)
25 ∗
Multi-speed setting (speed 5)
26 ∗
Multi-speed setting (speed 6)
27 ∗
Multi-speed setting (speed 7)
232 ∗
Multi-speed setting (speed 8)
233 ∗
Multi-speed setting (speed 9)
234 ∗
Multi-speed setting (speed 10)
235 ∗
Multi-speed setting (speed 11)
236 ∗
Multi-speed setting (speed 12)
237 ∗
Multi-speed setting (speed 13)
238 ∗
Multi-speed setting (speed 14)
239 ∗
Multi-speed setting (speed 15)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
* The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 180)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 4
Speed 3
(Low speed)
ON
RH
ON
ON
RM
ON
ON
RL
REMARKS
For multi-speed setting, if two or three speeds are simultaneously selected, priority is given to the set frequency of the lower
signal.
For example, when the RH and RM signals turn on, the RM signal (Pr. 5) has a higher priority.
The RH, RM, RL signals are assigned to the terminal RH, RM, RL in the initial setting. By setting "0 (RL)", "1 (RM)", "2 (RH)" in
any of Pr. 178 to Pr. 184 (input terminal function selection), you can assign the signals to other terminals.
Multi-speed operation
Jog operation
Remote setting function
Name
Initial Value
60Hz
30Hz
10Hz
9999
9999
9999
9999
9999
9999
9999
9999
9999
9999
9999
9999
(1) 3-speed setting (Pr. 4 to Pr. 6)
The inverter operates at frequencies set in Pr. 4 when RH signal is on,
Pr. 5 when RM signal is on and Pr. 6 when RL signal is on.
Speed 5
Speed 6
Speed 7
Time
ON
ON ON
ON
ON
ON

Frequency setting by external terminals

Parameter that should be Set
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Pr. 15, Pr. 16
Pr. 59
Setting Range
0 to 400Hz
Frequency when RH turns on
0 to 400Hz
Frequency when RM turns on.
0 to 400Hz
Frequency when RL turns on.
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
Frequency from 4 speed to 15 speed can
0 to 400Hz, 9999
be set according to the combination of
0 to 400Hz, 9999
the RH, RM, RL and REX signals.
0 to 400Hz, 9999
9999: not selected
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
0 to 400Hz, 9999
Refer to Page
95
97
99
Description