Multi-speed setting operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
Can be used to change the preset speed in the parameter with the contact terminals.
Any speed can be selected by merely turning on-off the contact signals (RH, RM, RL, REX signals).
Parameter
Name
Number
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
Multi-speed setting
24
(speed4)
Multi-speed setting
25
(speed 5)
Multi-speed setting
26
(speed 6)
Multi-speed setting
27
(speed 7)
Multi-speed setting
232
(speed 8)
Multi-speed setting
233
(speed 9)
Multi-speed setting
234
(speed 10)
Multi-speed setting
235
(speed 11)
Multi-speed setting
236
(speed 12)
Multi-speed setting
237
(speed 13)
Multi-speed setting
238
(speed 14)
Multi-speed setting
239
(speed 15)
* The setting range differs according to the inverter capacity. (22K or less/30K or more)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write