Mitsubishi Electric FR-D720-008 Instruction Manual page 188

Hide thumbs Also See for FR-D720-008:
Table of Contents

Advertisement

Communication operation and setting
(3)
Stop operation selection at occurrence of communication fault (Pr. 502)
Stop operation when retry count exceeds (Mitsubishi inverter protocol only) or signal loss detection error occurs can be selected.
Operation at fault occurrence
Pr. 502 Setting
0 (initial value)
1
2
Operation at fault removal
Pr.502 Setting
0 (initial value)
1
2
Automatic restart functions
Pr. 502 setting "0" (initial value)
Communication
OFF
fault
Fault display
(E.PUE)
Fault output
OFF
(ALM)
Pr. 502 setting "2"
Fault occurrence
Communication
OFF
fault
Fault display
(E.PUE)
Fault output
OFF
(ALM)
REMARKS
The fault output indicates fault output signal (ALM signal) or alarm bit output.
When the setting was made to provide a fault output, the fault description is stored into the faults history. (The fault description
is written to the faults history when a fault output is provided.)
When no fault output is provided, the fault definition overwrites the fault indication of the faults history temporarily, but is not
stored.
After the fault is removed, the fault indication returns to the ordinary monitor, and the faults history returns to the preceding fault
indication.
When the Pr. 502 setting is "1 or 2", the deceleration time is the ordinary deceleration time setting (e.g. Pr. 8, Pr. 44, Pr. 45). In
addition, acceleration time for restart is the normal acceleration time (e.g. Pr. 7, Pr. 44).
When "2" is set in Pr. 502, run command/speed command at restart follows the command before an fault occurrence.
When "2" is set in Pr. 502 at occurrence of a communication error and the error is removed during deceleration, the inverter
accelerates again at that point.
Parameters referred to
Pr. 7 Acceleration time, Pr. 8 Deceleration time
Pr. 190, Pr. 192 (output terminal function selection)
184
Operation
Coasts to stop
Decelerates to stop
Operation
Kept stopped
Fault occurrence
Fault removal
ON
Motor coasting
Display
ON
Fault removal
ON
OFF
Decelerates
to stop
Display
Refer to page 94
Indication
E. PUE lit
E. PUE lit after stop
Indication
E. PUE
Normal display
Pr. 502 setting "1"
Communication
OFF
fault
Time
Fault display
(E.PUE)
Fault output
(ALM)
Time
Refer to page 117
Fault Output
Provided
Provided after stop
Not provided
Fault Output
Kept provided
Not provided
Fault occurrence
OFF
ON
Decelerates to stop
OFF
Fault removal
OFF
Time
Display
ON

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-d740-012Fr-d710w-008Fr-d720s-008

Table of Contents