Omron CQM1H series Operation Manual page 87

Hide thumbs Also See for CQM1H series:
Table of Contents

Advertisement

Switch Settings
Terminator Setting Switch
Output Hold Setting Pin
Word Setting
Switch
4
3 (x 2
)
3
2 (x 2
)
2
1 (x 2
)
Word allocation
Output
of Master
Input
The terminator setting switch of the CQM1-LK501 I/O Link Unit mounted to the
CQM1H/CQM1 located at the end of the SYSMAC BUS system must be set to
ON.
Master
CQM1H/CQM1 (1)
If this pin is set to OFF, when an error has occurred, the CQM1H/CQM1's output
word (i.e., the Master's write word) will hold the value just before the error has
occurred. If this pin is set to ON, the value will be cleared.
0
0
0
0
0
1
0
1
0
Words
Words
Words
+0, 1
+4, 5
+8, 9
Words
Words
Words
+2, 3
+6, 7
+10, 11
Example
If pins 1 and 2 are set to OFF and pin 3 is set to ON on the CQM1-LK501 I/O Link
Unit, and the CQM1-LK501 I/O Link Unit is connected to the C200H Remote I/O
Master, the following words will be allocated on the C200H.
Output: words 216 and 217
Input: words 218 and 219
SYSMAC BUS system
Other Slave
Terminator setting switch
DIP switch (with output hold setting pin)
DIP switch
Output hold setting pin:
Word setting pins
(see table below)
Setting
0
1
1
0
1
0
Words
Words
+12, 13
+16, 17
Words
Words
+14, 15
+18, 19
Section 2-2
CQM1H/CQM1 (2)
Set
the
terminator
setting
switch of the CQM1-LK501 I/O
Link Unit mounted to this
CQM1H/CQM1 to ON.
1
1
1
0
1
1
1
0
1
Words
Words
Words
+20, 21
+24, 25
+28, 29
Words
Words
Words
+22, 23
+26, 27
+30, 31
67