Scaling Value Teach; Scaling Value Read - Omron CQM1H series Operation Manual

Hide thumbs Also See for CQM1H series:
Table of Contents

Advertisement

Commands and Responses

7-3-6 Scaling Value Teach

Command
Command Code
Parameter
Response

7-3-7 Scaling Value Read

Command
Command Code
Parameter
Response
This command can be used only when the timing hold in operation mode A is set
to normal.
This command is used to execute scaling value teaching. When scaling value
teaching is executed, the present input value can be used as the X1 or X2 scal-
ing value.
Parameters are not used with this command.
If the wrong command code is set to the output word, the following error code will
be set to the input word.
E000: This error code will be set to the input word if a nonexisting command code
is used.
E002: Teaching command execution error
E003: This error code will be set to the input word if the mode designation for this
command is not correct.
This command is used to read a scaling value.
Parameters are not used with this command.
If the output word is set to the correct command code, the sign of the scaling val-
ue and the scaling value will be set to the input word alternately in the following
format.
Teaching scaling value
0: X1
1: X2
Scaling value
0: X1
1: X2
2: Y1
3: Y2
Sign
0: Positive
F: Negative
Value
Range: 0 to 9999
Factory-set values:
X1 = 0, X2 = 1000,
Y1 = 0, and Y2 = 1000
Section 7-3
213

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cqm1 series

Table of Contents