Set Value Set; Set Value Teach - Omron CQM1H series Operation Manual

Hide thumbs Also See for CQM1H series:
Table of Contents

Advertisement

Commands and Responses

7-3-8 Set Value Set

Command
Command Code
Parameter
Response

7-3-9 Set Value Teach

Command
Command Code
Parameter
214
If the wrong command code is set to the output word, the following error code will
be set to the input word.
E000: This error code will be set to the input word if a nonexisting command code
is used.
This command is used to set the HH, H, L, or LL set value.
The set value will be stored in the nonvolatile memory and will not be lost after
the Unit is turned OFF.
Set value
0: LL
1: L
2: H
3: HH
If the correct command code or parameter is set to the output word, the same
command code or parameter will be set to the input word.
If the wrong command code or parameter is set to the output word, one of the
following error codes will be set to the input word.
E000: This error code will be set to the input word if a nonexisting command code
is used.
E001: This error code will be set to the input word if the parameter is not within
the range covered by the Unit.
This command can be used only when the timing hold in operation mode A is set
to normal.
This command is used to execute set value teaching. When set value teaching is
executed, the present input value can be used as the HH, H, L or LL set value.
Parameters are not used with this command.
Sign
0: Positive (Factory-set HH and H set values)
F: Negative (Factory-set LL and L set values)
Value
Range: 0 to 9999
Factory-set value: 9999
Teaching set value
0: LL
1: L
2: H
3: HH
Section 7-3