Commands and Responses
Response

7-3-5 Scaling Value Set

Command
Command Code
Parameter
Response
212
If the correct command code is set to the output word, the command code or pa-
rameter is set to the input word as a response.
If the wrong command code is set to the output word, the following error code will
be set to the input word.
E000: This error code will be set to the input word if a nonexisting command code
is used.
This command is used to set the X1, X2, Y1, or Y2 scaling value.
If the input type data is changed, the scaling value will be set to the factory-set
scaling value.
The set data will be stored in the nonvolatile memory and will not be lost after the
Unit is turned OFF.
If the wrong command code is set to the output word, the following error code will
be set to the input word.
E000: This error code will be set to the input word if a nonexisting command code
is used.
E001: This error code will be set to the input word if the parameter is not within
the range covered by the Unit.
Zero shift value storage area
1: RAM
2: Nonvolatile memory
Number of mean value processings
1: 1
2: 2
3: 4
4: 8
5: 16
Input sampling speed
1: Fast
2: Slow
Sign
0: Positive
F: Negative
Scaling value
0: X1
1: X2
2: Y1
3: Y2
Value
Range: 0 to 9999
Factory-set values:
X1 = 0, X2 = 1000,
Y1 = 0, and Y2 = 1000
Section 7-3