A Specifications - Omron CQM1H series Operation Manual

Hide thumbs Also See for CQM1H series:
Table of Contents

Advertisement

Standard Specifications
The standard specifications of the B7A Interface Unit conform to those of the CQM1H/CQM1 PC.
Performance Specifications
Item
I/O points
I/O word allocation
Communication method
Transmission distance
(see note 3)
Transmission delay time
Minimum input time
(see note 4)
Power consumption
External power supply
Weight
Dimensions
Note 1. Input mode setting allows selection between 16-point input and 15-point+1 error input.
2. Input mode setting allows selection between 32-point input and 30-point+2 error input. Refer to 2-2
Switch Settings.
3. The maximum transmission distance of the B7A Interface Unit varies with the transmission delay time
and the method of wiring. Refer to 3-1 Connections to B7A Link Terminals for details.
4. Minimum input time is the minimum required time to read an input signal from the CPU. The ON/OFF
signal range from the CPU to the B7A Interface Unit's output bit should be larger than the minimum input
time.
Appendix A
Specifications
B7A21: 16 input points (see note 1), 16 output points
B7A13: 32 input points (see note 2)
B7A03: 32 output points
B7A12: 16 input points (see note 1)
B7A02: 16 output points
B7A21: 1 word each for input and output (2 words in total)
B7A13: 2 words for input
B7A03: 2 words for output
B7A12: 1 word for input
B7A02: 1 word for output
Unidirectional, time-division multiplex
STANDARD:
500 m max.
RAPID:
100 m max.
STANDARD:
19.2 ms (rated delay), 31 ms max.
RAPID:
3 ms (rated delay), 5 ms max.
STANDARD:
16 ms
RAPID:
2.4 ms
100 mA at 5 VDC
12 to 24 VDC ±10% (excluding the power required by the B7A Link Terminals)
B7A21: 0.11 A min.
B7A13: 0.07 A min.
B7A03: 0.10 A min.
B7A12: 0.05 A min.
B7A02: 0.04 A min.
200 g max.
32 x 110 x 107 (W x H x D) mm
Specification
23

Advertisement

Table of Contents
loading

This manual is also suitable for: