Features And Word Allocations; Features; Word Allocations - Omron CQM1H series Operation Manual

Hide thumbs Also See for CQM1H series:
Table of Contents

Advertisement

Features and Word Allocations

2-1

Features and Word Allocations

2-1-1 Features

Temperature Control Units
Temperature Ranges
K (CA)
K (CA)
J (IC)
1800
1600
1300
1300
800
500.0
600
400
300
200
100
0
0.0
–100
–200
–200
0
1
2
Code
No.
1°C
0.1°C
1°C
Min.
unit

2-1-2 Word Allocations

234
• The PID with advanced feed-forward circuitry (2 degrees of freedom) of the
CQM1-TC20j/TC30j assures stable temperature control. The Units can
also be set to ON/OFF control.
• Temperature Control Units are available for either 4-loop temperature control
or 2-loop temperature control, and Units with 2-loop temperature control pro-
vide a heater burnout alarm. You can also select between thermocouples or
platinum resistance thermometers as the input sensors.
4 loops
2 loops with heater
burnout alarm
Thermocouples (See note.)
J (IC)
T (CC)
L
850
850
400.0
400.0
0.0
–100
–100
–200.0
3
4
5
0.1°C
0.1°C
1°C
Note K (CA) = Chromel/alumel, J (IC) = Iron/constantan, T (CC) = Copper/constan-
tan, L = Iron/constantan, R = Platinum/platinum rhodium 13%, S = Platinum/plat-
inum rhodium 10%, B = Platinum rhodium 30%/platinum rhodium 6%
• One word each is allocated to the Temperature Control Unit for inputs and out-
puts.
• Commands are used to set and read data.
• The IOTC(––) instruction can be used to simplify programming when using
CX-Programmer version 2.0 or higher and a CQM1H CPU Unit with a lot num-
ber of 0160 or later.
Inputs
Thermocouples
CQM1-TC201
Platinum
CQM1-TC302
resistance
thermometers
Thermocouples
CQM1-TC203
Platinum
CQM1-TC303
resistance
thermometers
L
R
S
B
1700
1700
1800
400.0
100
0.0
0
0
6
7
8
9
0.1°C
1°C
Section 2-1
Output type
NPN outputs
PNP outputs
CQM1-TC202
CQM1-TC302
CQM1-TC204
CQM1-TC304
Platinum resistance
thermometers
Pt100 JPt100
Pt100 JPt100
650.0
650.0
250.0
250.0
–20.0
–20.0
–200.0
–200.0
0
1
2
3
0.1°C
0.01°C
---
4 to
9
---

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cqm1 series

Table of Contents