Omron CQM1H series Operation Manual page 196

Hide thumbs Also See for CQM1H series:
Table of Contents

Advertisement

Timing Hold
Maximum Hold
Minimum Hold
176

From the moment the reset input is turned ON until the TIMING input is
turned ON for the first time after the reset input is turned OFF.
Power on

Input
TIMING input
Reset input
If the timing hold mode is set to maximum hold, the Unit continues data sampling
while the TIMING input is ON.
• When the TIMING input is turned OFF and the measurement mode is selected
using the data input function, the maximum value of the input data sampled
between the leading and trailing edge of the timing input is stored in the input
word as the scaled conversion data.
• When the TIMING input is turned OFF and the comparison mode is selected
using the data input function, the comparison result flags of the input word are
turned ON or OFF according to the comparison result processed by the Unit.
The Unit stops data sampling during the following periods, The scaled conver-
sion data is "BBBB."

From the moment the Unit is turned ON until the first timing input is turned
ON and OFF.

From the moment the reset input is turned ON until the timing input is ON
and OFF for the first time after the reset input is turned OFF.
Power on

Input
TIMING input
Reset input
If the timing hold mode is set to minimum hold, the Unit continues data sampling
while the TIMING input is ON.
• When the TIMING input is turned OFF and the measurement mode is selected
using the data input function, the minimum value of the input data sampled be-
tween the leading and trailing edge of the timing input is stored in the input
word as the scaled conversion data.
• When the TIMING input is turned OFF and the comparison mode is selected
using the data input function, the comparison result flags of the input word are
turned ON or OFF according to the comparison result processed by the Unit.
The Unit stops data sampling during the following periods, The scaled conver-
sion data is "BBBB."

From the moment the Unit is turned ON until the first timing input is turned
ON and OFF.

Sensing section

Section 2-2
Scaled conver-
sion data
Scaled conver-
sion data