Programming and Adjustment
–10 to 10 V
1, 2, 3...
6. Create the following program to scale values in a range between the lower
and upper-limit values and designate the lower- and upper-limit values that
have been monitored as parameters. Refer to page 89, Scaling for details.
00000
* "n" indicates the allocated word for analog input.
DM 0100
DM 0101
DM 0102
DM 0103
If the Analog Input Unit is set to a range of –10 to 10 V, follow the steps described
below to adjust the Analog Input Unit.
1. Refer to 3-1 Settings and connect the Analog Input Unit, CPU, and sensor or
transducer.
2. Connect a peripheral device such as a Programming Console to the CPU
and while referring to 3-3-1 Programming, create a program to convert 2's
complement.
Peripheral device
Sensing object
00000
Input condition
* "n" indicates the allocated word for analog input.
3. Obtain the minimum value of the sensing object. For a sensing operation, for
example, set the sensing object so that the output value of the sensor or
transducer will be minimum. For temperature measurement, it may be diffi-
cult to obtain the minimum value. In that case, instead of using the sensor or
transducer, use a reference power supply to obtain the output at the lowest
temperature.
Set value
0000
(BCD)
(Hexadecimal)
0100
Lower limit value
(BCD)
(Hexadecimal)
Upper limit value
PS
CPU
OUT
IPS
IN
Sensor or transducer
Section 3-3
SCL(66)
*
n
DM 0100
DM 0000
AD
AD
OUT
ANDW(34)
#0FFF
n
DM 0200
XORW(36)
#0800
DM 0200
DM 0200
93