5. The flue assembly shall be so placed or shielded as to
prevent ignition or damage to any part of any building.
6. The air inlet/products outlet duct and the terminal of the
boiler MUST NOT be closer than 25mm (1") to combustible
material. Detailed recommendations on the protection of
combustible material are given in BS. 5440-1:2008.
iMPo Rt Ant . It is essential to ensure, in practice, that products
of combustion discharging from the terminal cannot re-enter the
building or buildings through any openings into the building such
as ventilators, windows, doors, or other sources of natural air
infiltration, such as forced ventilation openings etc.
If products of combustion re-entry is identified or suspected this
should be immediately investigated and corrected following the
guidance provided in the current Gas Industry Unsafe Situation
Procedure.
Table 4 - Balanced Flue Terminal Position
f lue t erminal Positions
1. Directly below, above or alongside an opening
window, air vent or other ventilation opening.
2. Below guttering, drain pipes or soil pipes.
3. Below eaves.
4. Below balconies or a car port roof.
5. From vertical drain pipes or soil pipes.
6. From an internal or external corner or to a
boundary along side the terminal. BS5440-1 2008
7. Above adjacent ground, roof or balcony level.
8. From a surface or a boundary facing the terminal.
9. From a terminal facing a terminal.
10. From an opening in a car port
(e.g. door or window) into dwelling.
11. Vertically from a terminal on the same wall.
12. Horizontally from a terminal on the wall.
Vertical t erminals
13. Above the roof pitch with roof slope of all angles.
Above flat roof.
14. From a single wall face.
From corner walls.
15. Below velux window
16. Above or side of velux window
* Only one reduction down to 25mm is allowable per installation
otherwise BS5440-1 2008 dimensions must be followed.
vogue system boiler -
Min. Spacing*
300mm (12")
25mm ( 1")*
BS5440-1 2008
75mm (3")
25mm (1")*
BS5440-1 2008
200mm (8")
25mm (1")*
BS5440-1 2008
200mm (8")
25mm (1")*
BS5440-1 2008
150mm (6")
25mm (1")*
300mm (12")
300mm (12")
600mm (24")
1,200mm (48")
1,200mm (48")
1,500mm (60")
300mm (12")
300mm (12")
300mm (12")
300mm (12")
300mm (12")
2000mm (79")
600mm (24")
Installation and Servicing
GeneRAl
t e RMin Al
The terminal assembly can be adapted to accommodate various
wall thicknesses. Refer to Frame 10 .

AiR SUPPly

It is NOT necessary to have a purpose-provided air vent in the
room or internal space in which the boiler is installed. Neither is
it necessary to ventilate a cupboard or compartment in which the
boiler is installed, due to the low surface temperatures of the boiler
casing during operation; therefore the requirements of BS 6798,
Clause 12, and BS 5440:2 may be disregarded.
WAte R CiRCUl Ation Sy Ste M
iMPo Rt Ant.
A minimum length of 1 metre of copper pipe MUST be fitted to both
flow and return connections from the boiler before connection to
any plastic piping.
The central heating system should be in accordance with BS.6798
and, in addition, for smallbore and microbore systems, BS.5449.
WAte R t Re At Ment - see f rame 4
b oile R Cont Rol inte Rlo CKS
Central heating systems controls should be installed to ensure
the boiler is switched off when there is no demand for heating, in
compliance with Building Regulations.
Heating systems utilising full thermostatic radiator valve control
of temperature in individual rooms should also be fitted with a
room thermostat controlling the temperature in a space served by
radiators not fitted with such a valve.
When thermostatic radiator valves are used, the space heating
temperature control over a living / dining area or hallway having
a heating requirement of at least 10% of the minimum boiler heat
output should be achieved using a room thermostat, whilst other
rooms are individually controlled by thermostatic radiator valves.
However, if the system employs thermostatic radiator valves on all
radiators, or two port valves, then a bypass circuit external to the
boiler must be fitted with an automatic bypass valve to ensure a
flow of water should all valves be in the closed position.
e le Ct RiCAl SUPPly
Warning.
This appliance must be earthed.
Wiring external to the appliance MUST be in accordance with
the current I.E.E. (BS.7671) Wiring Regulations and any local
regulations which apply. For IE reference should be made to the
current ETCI rules for electrical installations.
The mains supply to the boiler and system wiring centre shall
be through one common fused double pole isolator and for new
heating systems, and where practical replacement installations, the
isolator shall be situated adjacent to the appliance.
Conden SAte d RAin
Refer to f rames 21 & 22
A condensate drain is provided on the boiler. This drain must be
connected to a drainage point on site. All pipework and fittings in
the condensate drainage system MUST be made of plastic - no
other materials may be used.
iMPo Rt Ant.
Installation must be in accordance with BS 6798.
The drain outlet on the boiler is sized for standard 21.5mm (3/4")
overflow pipe. It is a universal fitting to allow use of different
brands of pipework.
11