Chapter 5: Selecting test parameters
ENTER
3. Press
to accept.
NOTE: Once you start the conductance portion of the
VOLTS THEN CONDUCTANCE test, you will not be
able retest voltage. Be sure to review your voltage
reading before you start your conductance portion
of the test.
Selecting the string TEMPERATURE
The default is 25 °C (77 °F). Conductance measurements
vary by jar temperature. To compensate, the analyzer
uses the TEMPERATURE value to adjust the percentage of
the reference value you set in the UTILITIES SETUP as the
WARN/FAIL threshold. The percent is compensated to 25
°C (77 °F). Compensation is adjusted at 0.7% per degree
Celsius between 0 °C and 35 °C. (The kit includes an infrared
temperature sensor and instructions.)
ARROW
1. Press the
keys to highlight TEMPERATURE,
ENTER
and press
.
ARROW
2. Press the
keys (or use the numeric keypad) to
select a value.
ENTER
3. Press
to accept.
Saving the BATTERY SETUP
To save your settings for later use, press the
to highlight SAVE AND CONTINUE, and press
NEW test menu. To use a saved BATTERY
are returned to the
SETUP to test a string, see Selecting the TEST option in
Chapter 6: Testing.
To save your settings for immediate testing, connect the
clamps or probes and press the
AND TEST. Press
Testing.)
Adding jar model information to the database
To add new jar models and conductance reference values
to the database, use BATTERY MANAGER in the Main Menu.
The BATTERY MANAGER available in BATTERY SETUP allows
you to change a reference value only for a particular data
file. It does not save the change as a selection for new test
setups. You can also edit a model name or add a new model
using BATTERY MANAGER in the Main Menu.
Changing a reference value
1. Press the
AGER in the Main Menu, and press
2. Press the
press
3.
To change a reference value for a model in the database,
press the
ARROW
keys
press
ENTER
. You
4. In the EDIT MFGR screen, press the
28
•
•
ARROW
ENTER
to start the test. (See Chapter 6:
ARROW
keys to highlight the BATTERY MAN-
ARROW keys
to select a manufacturer, and
ENTER
.
ARROW keys
to select the model name, and
ENTER
.