Chapter 7: Test results and reports
Determining the strength of the string
To help you determine the strength of the string, use
the percentages of the reference value from
SUMMARY for all of the jar posts and straps. Table 7 lists
ranges of reference value percentages, jar condition, and a
recommended action to take.
Archiving test results
Archiving test data on site can help you:
• Compare results for changes or trends in string
performance
• Recognize when your string needs maintenance
or repair
%
o f
t h e
reference value
> 70%
60–69%
< 60%
Printing the STRING SUMMARY results
Turn on the printer by pressing the MODE button.
1.
ARROW keys
2. Press the
ENTER
and press
.
ARROW keys
3. Press the
MARY icon, and press
ARROW keys
4. Press the
ENTER
press
.
Table 7: String strength related to % of reference value
String strength
Good condition
Warning
Fail
to highlight the REPORTS icon,
to highlight the STRING SUM-
ENTER
.
to select the string name, and
• Provide warranty data for your supplier
Options
STRING
There are three ways you can archive test results using the
accessories included in the kit:
• Print test results with the IR printer
• Transfer test results to a PC through the IR receiver,
serial cable, and PC software
• Copy test results to a PC from the analyzer's
memory card
Recommended action
Check the jars for physical damage
Check for problems and refer to:
test results or other information about the string to
determine the cause of low readings
your company procedures for jar maintenance
IEEE standard 1188-1996: Recommended Practice
for Maintenance, Testing and Replacement of Valve-Regulated,
Lead-Acid (VRLA) Jars for Stationary Application
R e p l a c e t h e j a r s . R e f e r t o y o u r c o m p a n y j a r
r e p l a c e m e n t
p r o c e d u r e s
1188-1996
5.
Align the analyzer's IR transmitter (to the right of the
cable connector) with the IR receiver on the printer (be-
low the MODE button).
6. Press the
ter and receiver aligned for as long as it takes
to print.
7. Press the
Printing the JAR DATA results
44
o r
I E E E
PRINT
key. Keep the IR transmit-
BACK
key to end.
Celltron ULTRA
s t a n d a r d

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Celltron ULTRA and is the answer not in the manual?

Table of Contents

Save PDF