MINIMUM / MAXIMUM VERTICAL VENTING
TERMINATION
MINIMUM 3ft. (914mm)
MAXIMUM 31ft. (9.45m)
Figure 19a
HORIZONTAL & VERTICAL COMBINATION
IMPORTANT: THE HORIZONTAL VENT HEAT SHIELD MUST BE INSTALLED WHEN USING A 90-DEGREE ELBOW TO
HORIZONTALLY POSITION VENT SYSTEM.
IMPORTANT: KOZY HEAT WALL PASS-THRU, PART #800-WPT (4-1/2" (114mm) - 6-1/2" (165mm) WALL THICKNESS OR
#800-WPT2 (6-1/2" (165mm) - 12-1/2" (318mm) , MUST BE USED ON ALL HORIZONTAL VENT RUNS.
NOTE: Horizontal sections require 1/4" (6mm) rise for every 12" (305mm) of travel.
(12.9m)
40
38
36
34
32
30
28
26
24
22
(6.1m)
20
18
16
14
12
10
8
6
4
2
(ft.)
0
Figure 19b
VENTING
CAP
0 2 4 6 8
10 12 14 16 18 20 22 24 26 28 30
Termination must be
within shaded area
HORIZONTAL / VERTICAL COMBINATION:
(9.45m) 31' Vertical
(2.44m) 8' Horizontal
PAGE 19