GAS CONVERSION
This fireplace is manufactured for use with Natural Gas. An LP conversion kit is included with this fireplace.
Follow instructions included with conversion kit if converting to LP gas.
ATTENTION: The conversion shall be carried out in accordance with the requirements of the provincial authorities having jurisdiction and
in accordance with the requirements of the ANSI Z223.1 installation code.
CAUTION: Installation of the gas line must only be done by a qualified person in accordance with local building codes, if any.
If not, follow ANSI 223.1.
Commonwealth of Massachusetts: Installation must be done by a licensed plumber or gas fitter.
NOTE: A listed (and Commonwealth of Massachusetts approved) 12" (13mm) T- handle manual shut-off valve and flexible gas connector
(included) are connected to the 1/2" (13mm) control valve inlet. If substituting for these components, please consult local codes for
compliance.
NOTE: This fireplace is equipped with a 3/8"(10mm) x 18" (457mm) long flexible gas connector and manual shut-off valve. The gas line
should be run to the point of connection where the shut-off valve and flexible gas line will connect.
NOTE: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing
of that system at pressures in excess of ½ psi.
NOTE: The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any
pressure testing of the gas line at test pressures equal to or less than ½ psi (3.5 kPa).
NOTE: For high altitude installations, consult the local gas distributor or the authority having jurisdiction for proper rating methods.
IMPORTANT: The efficiency rating of this appliance is a product of thermal efficiency rating determined under continuous operating
conditions and was determined independently of any installed system.
MINIMUM INLET GAS PRESSURE
MAXIMUM INLET GAS PRESSURE
MANIFOLD PRESSURE
MANIFOLD PRESSURE (low setting)
ORIFICE SIZE
INPUT BTU/hr.
MINIMUM INPUT BTU/hr.

GAS LINE CONNECTION

NATURAL GAS
5.0 inches W.C. (7.0 W.C. recommended)
10.5 inches W.C.
3.5 inches W.C.
1.7 inches W.C.
#50
14,600
10,700
PAGE 13
#55616
LP GAS
11.0 inches W.C. (recommended)
13.0 inches W.C.
10.0 inches W.C.
6.5 inches W.C.
#57
14,700
10,700