NOTE: Horizontal sections require 1/4" (6 mm) rise for every 12" (305 mm) of travel.
NOTE: Page 17 has information on restrictor installation in conjunction with venting installation. Page 31 has information on
restrictor recommendations depending on burner flame appearance and instructions on installation after venting is completed.
NOTE: (2) 45° degree elbows may be used in place of (1) 90° elbow.
For each additional 90° elbow used after first elbow, 3 ft. (914 mm) must be subtracted from maximum allowed venting.
CAUTION: This gas appliance must not be connected to or joined with any other chimney flue serving another appliance.
WARNING: A WALL PASS-THRU MUST BE USED ON ALL HORIZONTAL VENT RUNS.
MAX. VERTICAL VENTING
TERMINATION
CAP
MAXIMUM 28 ft.
(8.53 m)
90˚ ELBOW
Figure 19a
VENTING
HOR. / VERT. COMBINATION
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
(12.9m)
40
38
36
34
32
30
28
26
24
22
(6.1m)
20
18
16
14
12
10
8
6
4
2
(ft.)
0
Figure 19b
PAGE 19
Termination must be
within shaded area