Ups Set-Up - MGE UPS Systems 4000 RT Installation And User Manual

Mge ups systems installation and user manual pulsar mx 4000 rt, 5000 rt
Table of Contents

Advertisement

4. Access to measurements and personalisation data

4.4 UPS set-up

Local settings
Function
Language
Date / Time Format
Date / Time Change
Audible Alarm
Output settings
Function
Output Voltage
Freq Converter
Output Frequency
Eco Mode
Slew Rate
Bypass Transfer
If bypass Ac nok?
Interrupt Time
Overload Prealarm
Redundancy Mode
ON/OFF settings
Function
Cold Start
Forced Reboot
Auto Restart
Energy Saving
Sleep Mode
Remote Command
- Page 26
34008030EN/AA
Factory setting
Options
English
French, German, Italian, Portuguese, Spanish
International
US (MM-DD-YYYY/HH:MM AM/PM)
(DD-MM-YYYY/HH :MM)
GMT + 1
MM-DD-YYYY/HH :MM adjustable
(Continental Europe)
Yes
No
Factory setting
Options
230 V
200 V / 208 V / 220 V /
240 V / 250 V
Disable
Enable
50 Hz
60 Hz
DisablE
Enable
1 Hz / sec.
0.5 Hz / sec.
Yes
No
10 ms
20 ms, ...... , 200 ms
105 %
40 %, 50 %, 70 %
No
Yes
Factory setting
Options
Disable
Enable
Enable
Disable
Enable
Disable
Disable
Enable
Enable
Disable
Enable
Disable
Comments
User selectable under frequency-
converter mode
See glossary
Transfer to bypass if Normal AC
source is out of tolerance
Break time calibration during load
transfer on Normal AC source out of
tolerance
Alarm if threshold is overrun
On parallel sequence : Alarm if
redundancy loss
Comments
Start on battery
Enables automatic restart of the
system even if Normal AC source is
restored before the end of the
shutdown sequence
UPS restarts automatically when
Normal AC source is restored
Automatic shutdown on battery if
output load level < 10 %
Enables consideration of shutdown
or restart orders from software to be
authorised

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pulsar mx 4000 rtPulsar mx 500 rt

Table of Contents