8.1 Technical specifications

Output power
Electrical supply network
Rated input voltage
Input voltage range
Frequency
Power factor
Leakage current
Load output
Voltage
Frequency
Harmonic distortion
Overload capacity
Battery
Environment
Operating temperature range
Relative humidity
Storage temperature range
Altitude
Noise level
(1) If the output voltage is 200V - 250V, the output power is 4500VA / 4000W.
(2) With one EXB module or more, the standard output power is 5000VA / 4000W.
(3) Values for 70% / 100% of UPS output.
(4) Programmable: 200V / 208V / 220V / 230V / 240V / 250V using the UPS Config software.
(5) Frequency-converter mode is programmable using the UPS Config software.
Pulsar MX 4000
Pulsar MX 5000
4000 VA /
3600 W
Single phase 230 V
120 / 156 V to 280 V
50/60 Hz (autoselection)
> 0.99
7 mA max.
Single phase 230 V ±3%
50/60 Hz ±0,5%
< 3%
105% continuous, 110% 2min,
125% 1min, > 150% 0.5s
15 x 12V - 5 Ah,
15 x 12V - 5 Ah,
sealed lead acid,
sealed lead acid,
maintenance free
maintenance free
20% to 90% (non-condensing)
0 to 1000 m without derating
< 45 dBA

8. Appendices

Pulsar MX EXB
(1)
5000 VA
/
(2)
4500 W
(3)
(4)
(5)
Two 15 x 12 V - 5 Ah
strings, sealed lead acid,
maintenance free
0°C to 40°C
-25°C to 40°C
34008030EN/AA