MGE UPS Systems 4000 RT Installation And User Manual

MGE UPS Systems 4000 RT Installation And User Manual

Mge ups systems installation and user manual pulsar mx 4000 rt, 5000 rt
Table of Contents

Advertisement

www.mgeups.com
Pulsar MX
4000 RT
5000 RT
Installation and user
manual
34003641FR/AA
- Page 1

Advertisement

Table of Contents
loading

Summary of Contents for MGE UPS Systems 4000 RT

  • Page 1 Pulsar MX 4000 RT 5000 RT Installation and user manual - Page 1 34003641FR/AA...
  • Page 2 - Page 2 34008030EN/AA...
  • Page 3 Before installing Pulsar MX, please read the booklet on the required safety instructions. Then follow the indications in this manual. To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar MX range, we invite you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative.
  • Page 4 Introduction Pictograms Important instructions that must always be followed. Information, advice, help. Visual indication. Action. Audio signal. In the illustrations on the following pages, the symbols below are used: LED off LED on - Page 4 34008030EN/AA...
  • Page 5: Table Of Contents

    Standard positions ... 7 Tower position ... 7 Rack position ... 7 Rear panels... 8 Pulsar MX 4000 RT / 5000 RT... 8 Pulsar MX EXB RT (optional battery module)... 8 Display and control panel ... 9 Options ... 9 Rack mounting kit ...
  • Page 6 Contents Troubleshooting Troubleshooting LEDS (21) and (22)...28 Troubleshooting not requiring MGE UPS SYSTEMS after-sales support ...28 Troubleshooting requiring MGE UPS SYSTEMS after-sales support...29 Life Cycle Monitoring (LCM) Description...30 Get free offers...30 Secure your installation power continuity ...30 Reset or disable LCM ...31 Maintenance Hot swapping the power sub-module...32...
  • Page 7: Presentation

    Tower position Rack position 1. Presentation Dimensions (H x W x D) in mm / Inches Pulsar MX 4000 RT 444.5 x 131 x 700 / 17.5 x 5.16 x 27.56 Pulsar MX 5000 RT 444.5 x 131 x 700 / 17.5 x 5.16 x 27.56...
  • Page 8: Rear Panels

    1. Presentation 1.2 Rear panels Pulsar MX 4000 RT / 5000 RT Pulsar MX EXB RT (optional battery module) - Page 8 34008030EN/AA (1) Two groups of 2 programmable (10A) outlets for connection of equipment (2) Groups of 4 (10A) outlets for connection of...
  • Page 9: Display And Control Panel

    1.3 Display and control panel 1.4 Options Rack mounting kit Telescopic rails for Pulsar MX RT mounting in 19’’ enclosure with mounting hardware (part number 68002) 1. Presentation (20) Load protected LED (21) Downgraded operation LED (22) Load not protected LED (23) Alphanumeric display (24) Escape (cancel) button (25) (26) Function buttons...
  • Page 10: Modulareasy Mx

    1. Presentation ModularEasy Example of Pulsar MX ModularEasy connected with two UPSs in parallel operation - Page 10 34008030EN/AA Pulsar MX ModularEasy enables parallel operation when combining two Pulsar MX UPSs. Consequently you can enhance the availbility level of your equipment (N+1 redundancy).
  • Page 11: Battery Extensions For Ups Backup Times Up To 80 Minutes

    Battery extensions for UPS backup times up to 80 minutes (at full load) Pulsar MX RT offers a standard backup time of 5/7 minutes at full load. To increase backup time, it is possible to connect Pulsar MX EXB RT modules to the UPSs. Battery extensions for Pulsar MX RT Battery Integration System Battery extension cable (1,8 m / 6 ft)
  • Page 12: Installation

    2. Installation 2.1 Unpacking and contents check (40) Pulsar MX 4000 or 5000 UPS. (41) Two sets of tower stands. (42) RS232 communications cable (43) Product documentation. (44) 4 cable lockers. (45) Telescopic rails for rack enclosure with mounting hardware (optional, or standard with NetPack version). Packaging must be destroyed according to waste management standards.
  • Page 13: Installation In Tower Position

    2. Installation 2.3 Installation in tower position Follow steps 1 to 3 to adjust the tower stands for the upright position. Always keep 150 mm free space behind the UPS rear panel. The distance between the tower stands should be 450 mm. - Page 13 34008030EN/AA...
  • Page 14: Installation In Rack Position

    2. Installation 2.4 Installation in rack position Adjustment of the orientation of the logo and control panel UPS module rack mounting (optional rails required) Pulsar MX RT is very heavy. To ease its rack integration, we strongly recommend to remove the battery tray as shown below: 1 - Remove the 6 fixing screws to free the main front panel bezel.
  • Page 15: Ups Or Battery Module Rack Mounting

    Follow steps 1 to 4 for rack mounting the UPS onto the rails. The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS. Note for step 1: it is possible to adjust the position of both front mounting ears.
  • Page 16: Communication Ports

    Pulsar MX RT provides 3 communication methods that can be used simultaneously: ◗ 2 COM ports provide RS232 or USB communications using MGE UPS SYSTEMS SHUT protocol. Compatible with most power management software applications available into the enclosed Solution Pac CD-Rom. Please, note that both ports cannot be used at the same time.
  • Page 17: Remote Power Off Communication Port

    Remote Power Off communication port (16) (see page 8) Installation of a Remote Power Off function must be carried out in compliance with applicable regulations. In order to fully de-energize devices and Pulsar MX RT with the RPO port, it is necessary: ◗...
  • Page 18: Required Protective Devices And Cable Cross-Sections

    2. Installation 2.6 Required protective devices and cable cross-sections Recommended upstream protection UPS power rating 4000 RT 5000 RT 2 poles circuit breaker Recommended downstream protection UPS power rating 4000 RT 5000 RT Required cable cross-sections ◗ Terminal-block cable capacity: 6 mm ◗...
  • Page 19: Connection Of Input/Output Power Cables To Ups Terminals

    2.7 Connection of input/output power cables on UPS terminals ◗ This type of connection must be carried out by qualified electrical personnel. ◗ Before carrying out any connection, check that the battery circuit breaker (19) (see page 8) and that the upstream protection device (Normal AC source) is open ("0").
  • Page 20: Connection Of Iec Cables To Output Receptacles

    2. Installation 2.8 Connection of IEC cables to output receptacles - Page 20 34008030EN/AA 1 - Connect the equipments to the UPS using the cables (49). It is preferable to connect the priority equipments to the four outlets (2) and the non priority equipments to the four outlets (1) that can be programmed in pairs (1 and 2).
  • Page 21: Operation

    3.1 Initial start-up It is essential to contact our Customer Service to ensure that your system is commissionned in complete safety and to benefit from the manufacturer’s guarantee. UPS personalisation If UPS personalisation is desired, it is advised to enter the personalisation mode at this time (see the 4.4 section).
  • Page 22: Operating Modes

    3. Operation 3.3 Operating modes Normal mode Eco mode - Page 22 34008030EN/AA This is the standard operating mode, set by default in the factory. Under normal condition (Normal AC source available): LED (20) is ON. LEDs (30), (32), (34) are green. The equipments are protected by the UPS.
  • Page 23: Operation On Battery Power

    3.4 Operation on battery power When the Normal AC source is not available, the load continues to be protected by the UPS. Power is supplied by the battery. Transfer to battery power Low battery warning End of backup time 3.5 Return on Normal AC source After an outage, the UPS restarts automatically when Normal AC source is restored (unless this function has been disabled via UPS personalisation) and the load is supplied again.
  • Page 24: Ups Shutdown

    3. Operation 3.6 UPS shutdown - Page 24 34008030EN/AA " " 1 - Press the button (28) more than 3s. The buzzer beeps once, and the load is no longer protected by the UPS. It is powered via the Normal AC source. If the UPS is set in frequency converter mode, the equipments will not be powered.
  • Page 25: Access To Measurements And Personalisation Data

    4. Access to measurements and personalisation data 4.1 Display organisation 4.2 Access to measurements Press the scroll button (24) (see section 1.3, page 9) to access measurements for voltage, current, frequency, power output and battery capacity. 4.3 Access to UPS set-up and maintenance using the control panel (23) ◗...
  • Page 26: Ups Set-Up

    4. Access to measurements and personalisation data 4.4 UPS set-up Local settings Function Language Date / Time Format Date / Time Change Audible Alarm Output settings Function Output Voltage Freq Converter Output Frequency Eco Mode Slew Rate Bypass Transfer If bypass Ac nok? Interrupt Time Overload Prealarm Redundancy Mode...
  • Page 27: Maintenance

    " " Advanced settings UPS settings Comments 1% increment 5 Ah increment Protection against deep discharge. If disable, MGE UPS SYSTEMS warranty will be void Comments Serial number Soft version Technical level 10 alarms can be stored automatically Life cycling monitoring alarms You need to register at www.mgeups.com/Icm to get the...
  • Page 28: Troubleshooting

    5. Troubleshooting 5.1 Troubleshooting LEDS (21) and (22) 5.2 Troubleshooting not requiring MGE UPS SYSTEMS after-sales support " " Press the Enter button (27) to display the details below : Displayed details NO BATTERY I/O BAD CONNECTION NO POWER MODULE...
  • Page 29: Troubleshooting Requiring Mge Ups Systems After-Sales Support

    5.3 Troubleshooting requiring MGE UPS SYSTEMS after-sales support Display POWER MODULE FAULT BATT MODULE FAULT FRAME FAULT Note: In case of multiple fault, press the Troubleshooting one UPS (or two UPS in parallel) with ModularEasy module: Indication The equipments are no longer supplied...
  • Page 30: Life Cycle Monitoring (Lcm)

    %, Battery ambient temperature, time on inverter, time on mains 2 Signification Entrust your product commissioning to MGE UPS SYSTEMS: MGE UPS SYSTEMS will check the installation according to local regulations, in respect of the state of the art. Get your product warranty extension, contacting MGE UPS SYSTEMS at: www.mgeups.com/lcm...
  • Page 31: Reset Or Disable Lcm

    Reset or disable LCM In case of any LCM messages displayed: For temporary reset: press the escape button (24) more than 3 seconds, into Status and Alarm ◗ the alarm status. The alert will be repeated twice each 30 days. ◗...
  • Page 32: Maintenance

    7. Maintenance 7.1 Hot swapping the power sub-module This operation must be carried out by qualified electrical personnel only. This operation can be performed without interrupting the equipments. Disconnecting the power sub-module : Reconnecting the power sub-module : ◗ Carry out the above instructions in reverse order. ◗...
  • Page 33: Maintenance On A Ups Equipped With The Modulareasy Mx Module

    Carry out the above instructions in reverse order. ◗ To ensure safety and high performance, use only batteries supplied by MGE UPS SYSTEMS. 7.3 Maintenance on a UPS equipped with the ModularEasy MX module Before any action on the manual bypass (61) located on the ModularEasy module front panel, always check that the inverter is stopped (press the "0"...
  • Page 34: Training Centre

    7. Maintenance 7.4 Training centre To fully master operation of your MGE UPS SYSTEMS product and carry out level 1 servicing, see our complete range of technical training courses, available in both French and English. 50 Hz training centre MGE UPS SYSTEMS...
  • Page 35: Appendices

    8.1 Technical specifications Output power Electrical supply network ◗ Rated input voltage ◗ Input voltage range ◗ Frequency ◗ Power factor ◗ Leakage current Load output ◗ Voltage ◗ Frequency Harmonic distortion ◗ ◗ Overload capacity Battery Environment ◗ Operating temperature range ◗...
  • Page 36: Glossary

    It is possible to modify certain UPS parameters set in the factory. Certain UPS functions can also be modified by the MGE UPS SYSTEMS power management products to better suit user needs. These outlets can be automatically shut down during operation on battery power (shutdown time delays can be programmed with the MGE UPS SYSTEMS power management products).
  • Page 37 - Page 37 34008030EN/AA...
  • Page 38 MGE UPS SYSTEMS T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R 140, Avenue Jean Kuntzmann ZIRST - Montbonnot St Martin 38334 - Saint Ismier Cedex - France www.mgeups.com...

This manual is also suitable for:

Pulsar mx 4000 rtPulsar mx 500 rt