Personalization; Functions; Ups Driver Install - MGE UPS Systems Comet EXtreme Series Installation And User Manual

Hide thumbs Also See for Comet EXtreme Series:
Table of Contents

Advertisement

Comet EXtreme 4.5/6/9/12 kVA
Sleep mode
Return of AC input power
3.6

Personalization

3.6.1
Function
Note: Manual Bypass Switch must be in normal mode during personalization.
Note: 240 VAC can be applied to the UPS prior to completion of personalization.
Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer that
is connected to the UPS (see section 2.7 Connection to the RS 232 communications port).
Check that the RS232 cable "24" is correctly connected and that the battery circuit breaker "2" is closed.
3.6.2
"UPS Driver" Installation
1. Insert the "UPS Driver" diskette in the drive of an IBM-compatible microcomputer.
2. Select the disk drive (A :\).
3. Double-click "upsdriv.exe".
Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing a number of tabs,
each presenting a set of parameters.
Note: Verify that AC input and output voltages are correct at I/O Box in/out terminal block, according to
UPS personalization and your application.
Table 3-1: Personalization Functions tables.
"ON/OFF conditions" tab
Personalization function
Automatic start
Cold start (battery power)
Forced shutdown
Sleep mode
UPS ON / OFF via software
"Battery" tab
Personalization function
"Battery test: intervals
"Low-battery shutdown
warning" threshold
page 3—6
This operating mode may be personalized using the "UPS Driver" software.
Sleep mode saves battery power when no equipment is connected to the UPS.
The UPS automatically restarts when the AC-power source returns to within toler-
ances.
If, in spite of the return of AC input power, the UPS does not restart, check that the
automatic-restart function (activated by return of AC input power) has not been
disabled
Default setting
Enabled
Enabled
Enabled
Disabled
Enabled
Default setting
Every day
20% remaining battery
back-up time
Operation
Options
Once a week
Once a month
No test
40% remaining
battery back-up time