Connection In Other Grounding Environments - H3C S12500 Installation Instructions Manual

Routing switches
Hide thumbs Also See for S12500:
Table of Contents

Advertisement

Step1 Remove the screw from the grounding hole on the switch chassis.
Step2 Put the supplied OT terminal of the PGND cable on the grounding screw.
Step3 Insert the grounding screw into the grounding hole and screw it down.
Step4 Connect the other end of the PGND cable to the grounding strip of the cabinet.
Figure 3-6 Connect the PGND cable
(1) Grounding hole

Connection in Other Grounding Environments

Following are some methods for grounding the switch in different grounding environments that you are
likely to encounter when installing the switch at different places.
When a grounding strip is available at the installation site, attach one end of the yellow-green
PGND cable of the switch to the grounding screw on the grounding strip and fasten the grounding
screw.
The fire main and the lightning rod of the building are not good grounding options. The PGND cable of
the switch should be connected to the earthing system of the equipment room.
(2) Grounding screw
3-6
(3) PGND cable