Grounding The Switch In Other Grounding Environments - H3C S5500-EI Series Installation Manual

Hide thumbs Also See for S5500-EI Series:
Table of Contents

Advertisement

Figure 28 Grounding the switch by burying the grounding conductor into the earth ground
(1) Grounding screw
(4) Joint

Grounding the switch in other grounding environments

Grounding an AC-powered switch
If the installation site has no grounding strips or earth ground, you ground an AC-powered switch through
the PE wire of the AC power supply.
Make sure the PE wire is well connected to the ground at the power distribution room or AC transformer
side, the switch PE terminal and the PE wire are well connected, and the three-wire input cable of the
grounding cable is used for the power supply cable. If the PE wire of the AC power supply is not
grounded at the power distribution room or AC transformer side, report the problem and reconstruct the
grounding system.
Figure 29 Grounding through an AC power PE wire
(1) Three-wire AC power input cable
Grounding a DC-powered switch
If the installation site has no grounding strips or earth ground, you ground a DC-powered switch through
the return wire (RTN) of the DC power supply, and make sure this RTN wire is well connected to the
ground at the DC output of the DC power cabinet.
(6)
(2) Grounding cable
(5) Grounding conductor
(2) Switch rear panel
35
(1)
(2)
(3)
(4)
(5)
(3) Earth ground
(6) Switch rear panel