Number - Mitsubishi F940GOT-SWD-E Operation Manual

Graphic operation terminals melsec-got
Hide thumbs Also See for F940GOT-SWD-E:
Table of Contents

Advertisement

Graphic Operation Terminal F940GOT
10.4.2

Number

The "Number" object displays the data stored in a word device in the PLC.
u u u u Contents of setting
Attribute
Position
Bg and Fg
Character Size
Digits and Deci-
mal Point At
Format
Word Device
Style
Shift
Gain 1, Gain 2
and Offset
Data Changeable
Minimum Value
and Maximum
Value
User ID and Des-
tination ID
Frame
Frame Color
1) Digits
• Maximum allowable number of digits: 12 (Each of "-" (minus sign) and a decimal point is
counted as one digit.
Example:)
High-speed counter
Enter the X and Y coordinates in the unit of dot.
Enter the background color and the numeric color. (Initial values: White and
black)
Enter the width (W) and the height (H) of characters. The available sizes are
×0.5, ×1, ×2, ×3 and ×4.
Enter the total number of digits.
Enter the number of digits after decimal point.
Set the numerical display format. (Initial value: None)
Enter a word device whose data is to be displayed as a numeric.
Enter "Data Size" and "Displayed value (Current or Preset)" also.
Select the numeric format among "Decimal (with/without sign)", "Decimal
(leading 0) (with/without sign)", "Hexadecimal", "Octal", "Binary" and "Real".
Select the layout among "Right", "Center" and "Left".
(Monitor value × Gain 1 / Gain 2) + Offset
The result of this arithmetic operation is displayed.
Set whether or not the data of the specified device can be changed using
the keys.
Set the lower limit and the upper limit of a numeric which can be entered to
a word device while "Data Changeable" is made effective with a check mark.
Select "Direct" (to enter a desired value) or "Indirect" (to enter a desired data
register).
These attributes are effective while "Data Changeable" is made effective
with a check mark.
Enter an object to be displayed next when a cursor control key is pressed.
Select the frame to be displayed around the numeric. (Initial setting: No
frame)
Enter the frame color. The area inside the frame is filled with the background
color.
C235 (32 bits)
to
-2147483648
-2147483648
11 digits
Creation of Display Screens (FX-PCS-DU/WIN-E) 10
Contents of setting
If data whose number of digits exceeds the maximum allowable
number of digits is specified to be displayed, "?" is displayed.
10 digits
ß1)
ß2)
ß3)
ß4)
ß5)
ß6)
ß7)
ß8)
10-15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F940got-lwd-e

Table of Contents