ZONE 1 THROUGH 4 FIRST STAGE DIFFERENTIAL
Differential is the temperature between when first stage will cycle ON and cycle
OFF. (Example: Zone 1 HD Display is set at 70°F with a 1.0°F differential. Cooling
Demand - cooling will cycle ON when the room temperature reaches 70.5°F and
cycle OFF when the room temperature is 69.5°F)
Range is 0.5 to 3°F. Default is 1°F. Adjustments are in increments of 1°F.
NOTE: For XC/XP 25 differentials are ignored.
ZONE 1 THROUGH 4 CONTINUOUS BLOWER CFM
Minimum and maximum CFM will be dependent on system component
configurations. These parameter values are automatically adjusted to the specific
hardware configuration. See iHarmony
minimum CFMs for specific indoor units.
Zones requesting the fan ON are only allowed while no other zone demand is
®
present. The iComfort
S30 will sum all the zone continuous blower CFM
requirements and send the command only after positioning the dampers and
waiting for the damper close delay period to expire (30 seconds) Continuous
blower demands are the lowest priority demands, all other conditioning demands
will over-ride the continuous blower demand.
Range is 5 to maximum of indoor unit. Default is dependent on tonnage of indoor
unit. Adjustments are in increments of 5 CFM.
ZONE 1 THROUGH 4 COOLING CFM
Minimum and maximum CFM will be dependent on system component
configurations. These parameter values are automatically adjusted to the specific
hardware configuration. See iHarmony
minimum CFMs for specific indoor units.
Target cooling CFM for a specific zone. Range is 5 to maximum of indoor unit.
Default is dependent on tonnage of indoor unit. Adjustments are in increments of 5
CFM. Adjustments are in increments of 5 CFM.
ZONE 1 THROUGH 4 HEATING CFM
Minimum and maximum CFM will be dependent on system component
configurations. These parameter values are automatically adjusted to the specific
hardware configuration (See table 9 in iHarmony installation instructions or on the
right side of this page for minimum CFMs for specific indoor units.
Target heating CFM for a specific zone. Range is 5 to maximum of indoor unit.
Default is dependent on tonnage of indoor unit. Adjustments are in increments of 5
CFM. Adjustments are in increments of 5 CFM.
®
zoning system installation instruction for
®
zoning system installation instruction for
ADVANCED SETTINGS
Options available are:
S
Restart Smart Hub (reboots Smart Hub).
S
Reset Smart Hub (erases Smart Hub settings and restarts installer setup).
S
Reconfigure system (erases all system settings and restarts installer setup).
The following is information on all possible available parameters. Parameters listed
are dependent on actual type of heat pump installed.
ABOUT
This screen provides information concerning language supported, equipment type
name, unit model number, unit serial number, unit nominal capacity, number of
heating states, number of cooling stages, heating capacity by stage, cooling
capacity by stage, control software revision, control model number, control serial
number, control hardware revision, outdoor air temp sensor, protocol revision
number, device product level, 24VAC average power consumption, 24VAC peak
power consumption, line voltage average power consumption, line voltage peak
power consumption, outdoor inverter model number, outdoor inverter firmware
version, outdoor fan RPM profile, unit code, compatible devices list, application
code memory size and micro-controller part number.
EQUIPMENT NAME
A unique name can be assigned to this component. Name can be up to 29
characters. Name can consist of letters, numbers, special characters and spaces.
COMPRESSOR SHORT CYCLE DELAY
The range is 60 - 300 seconds. Default is 300 seconds and with an incremental
adjustment of 60 seconds.
This feature prevents the compressor from being short cycled any time the
compressor is turned "OFF"
DEFROST TERMINATION TEMP
The range is 50 - 100°F. Default is 50°F and with an incremental adjustment of
10°F.
This is the temperature that defrost mode will be terminated.
COMPRESSOR SHIFT DELAY ON/OFF
The options are ON or OFF. By default it is set to ON.
S
Shift Delay "OFF" - Compressor will not be cycled "OFF" going in and out of
defrost.
S
Shift Delay "ON" - Compressor will be cycled "OFF" going in and out of defrost.
22