Ry35 And Ry45 - Daikin Sky Air R-407C Service Manual

Sky air r-407c b-series
Table of Contents

Advertisement

ESIE02–01
3.5

RY35 and RY45

Technical
The table below contains the technical specifications.
specifications
Specification
Compressor
Heat exchanger
Fan
Refrigerant circuit
Safety and functional devices
Heat insulation
Weight
Electrical
The table below contains the electrical specifications.
specifications
Specification
Unit
Fan motor
Part 1 – System Outline
RY35EAZ7V1
Model x No.
1YC43BTV1
Type
Hermetically sealed swing type
Crankcase heater
Refrigerant oil type
FVC68D + HAB15D
No. x motor output
1 x 1300 W
Speed
2850 rpm
No. of cylinders
1
Oil charge
850 cc
Length
805 mm
Rows x stages x fin pitch
1 x 24 x 2.0 mm
No. of passes
1.67
Face area
0.513 m²
Tube type
Hi-XA
Fin type
WL fin
Empty tubeplate hole
0
No. of fans
1
Nominal air flow (230 V) cooling
36 m³/min
Nominal air flow (230 V) heating
32 m³/min
Fan motor model
19TFB6062
Nominal speed (230 V)
H: 610 rpm
L: 350 rpm
Fan speed
2 steps
Type
R407C
Charge
1.1 kg
No. of circuits
Max. 1
See page 1–71
Both liquid and gas pipes
50 kg
RY35EAZ7V1
Phase
1~
Voltage
230 V
Frequency
50 Hz
No. of wire connections
3 for power supply (including earth wire)
4 for connecting with indoor (including earth wire)
Nominal running current (cool-
6.9 A
ing)
Nominal running current (heat-
6.4 A
ing)
Starting current (cooling)
34 A
Starting current (heating)
34 A
Recommended fuses
16 A
Power supply intake
Outdoor unit only
No. of motors x output
1 x 30 W
Specifications
RY45EAZ7V1
1YC56ATV1N
1 x 1700 W
2860 rpm
788 mm
2 x 24 x 2.0 mm
3
0.481 m²
31 m³/min
28 m³/min
2.0 kg
57 kg
RY45EAZ7V1
9.1 A
8.8 A
42 A
42A
20 A
1–61
1
3
4