Daikin Sky Air R-407C Service Manual page 268

Sky air r-407c b-series
Table of Contents

Advertisement

Error Codes: Outdoor Units
1
High temperature of
compressor head
3
3
4
5
3–38
To troubleshoot, proceed as follows:
Compressor head temperature > 120 °C
or
Discharge superheat > 55 °C
Check the stop
valves.
Are they
open?
Yes
Check the
refrigerant piping
circuit.
Is
it clogged?
Yes
Replace clogged
part.
Open the stop
No
valve(s).
Check the
No
refrigerant level.
Is the
refrigerant filled to
the proper level?
Yes
Check the
compressor.
Is it
malfunctioning?
Yes
Replace
compressor.
ESIE02–01
Fill to specified
No
level
Check expansion
valve and
No
discharge pipe
thermistor.
Part 3 – Troubleshooting

Hide quick links:

Advertisement

Table of Contents
loading