Functions Of Thermistors: Small Heat Pumps - Daikin Sky Air R-407C Service Manual

Sky air r-407c b-series
Table of Contents

Advertisement

General Functionality
1.2

Functions of Thermistors: Small Heat Pumps

1
Locating the
thermistors
2
3
4
Functions of the
thermistors
5
2–4
The thermistors on the illustration below are used to control the system. This control secures a proper
operation and prevents problems of the unit.
Outdoor unit
The table below contains the functions of the small h/p.
Ther-
Wiring
Location
mistor
symbol
1
Indoor heat
R2T
exchanger
2
Indoor air
R1T
return
3
Outdoor heat
R2T
exchanger
4
Outdoor air
R1T
return
3
4
Mode
Function
Cooling
Freeze-up thermostat
Heating
Hot start indoor fan
Peak cut-off
Cooling
Thermostat control
Heating
Thermostat control
Cooling
Not used
Heating
Frost prevention and overload prevention
Defrost initiation and termination
Cooling
Low ambient control
Heating
Frost prevention
Defrost initiation
ESIE02–01
Indoor unit
2
1
Part 2 – Functional Description