Pcb Type F - Daikin Sky Air R-407C Service Manual

Sky air r-407c b-series
Table of Contents

Advertisement

ESIE02–01
8.9

PCB Type F

Applicable
The table below contains the applicable PCB numbers and units of this PCB type.
PCB No.
2P060444-1 (or EC0060A)
2P060445-1 (or EC0061A) (illustrated below)
PCB
The illustration below shows the PCB connectors.
Connectors
The table below describes the PCB connectors.
Connector
X5A
X10A
X11A
X15A
X18A
X19A
X21A
X23A
X25A
X27A
X30A
X33A
X35A
X50A
Part 1 – System Outline
X15A
X23A
X18A
X19A
X30A
X35A X10A
Connected to
X1M
T1R
T1R
33H
R2T
R1T
M1F
M3P
X2M
X1A (KRP4)
Unit
FHYBP35/45/60/71B7V1
FHYBP100/125B7V1
X33A
X11A
X25A
X50A
X5A
Description
Terminal strip (P1 and P2)
Transformer 230V/22V secundary
Transformer 230V/22V primary
Float switch
Heat exchanger thermistor
Air thermistor
Fan motor
Connector to capacity adaptor
Drain pump motor
Power supply and communication to the outdoor unit
Connector to interface adaptor for Sky Air series (DTA102)
Connector to adaptor for wiring (option KRP1B)
Connector to group control adaptor power supply (16 VDC) for
optional PCB KRP4
In case no transfo is used: Connector to power supply PCB
PCB Layout
X27A
1
3
4
X21A
5
1–153