Pcb Type R - Daikin Sky Air R-407C Service Manual

Sky air r-407c b-series
Table of Contents

Advertisement

ESIE02–01
8.18

PCB Type R

Applicable
The table below contains the applicable PCB number and unit of this PCB type.
PCB No.
2P060448-1 (illustrated below)
PCB
The illustration below shows the PCB connectors.
Connectors
The table below describes the PCB connectors.
Connector
X5A
X10A
X11A
X14A
X15A
X18A
X19A
X20A
X23A
X24A
X25A
X26A
X27A
X29A
X30A
X35A
X98A
Part 1 – System Outline
X27A
X11A
X98A
X20A
Connected to
X1M
X2A on A2P
X1A on A2P
33A
R2T
R1T
M1F
X2A on A3P
M1F
X2M
M1A
X1A (KRP4)
C1R
Unit
FAYP71/100BV1
X5A
X10A
X25A X29A X24A X35A X26A X30A X14A X15A
Description
Terminal strip (P1 and P2)
Power supply PCB
Power supply PCB
Limit switch (swing flap)
Float switch
Heat exchanger thermistor
Air thermistor
Fan motor power supply
Connector for capacity adaptor
X24A is connected when the wirelesss remote control is used
Drain pump motor
Fan motor feedback cable
Power supply and communication to the outdoor unit
Swing flap motor
Connector to interface adaptor for Sky Air series (DTA102)
Connector to group control adaptor power supply (16 VDC) for
optional PCB KRP4
Capacitor (M1F)
PCB Layout
X23A
X18A
X19A
1–163
1
3
4
5

Hide quick links: