Malfunctioning Electronic Expansion Valve - Daikin Sky Air R-407C Service Manual

Sky air r-407c b-series
Table of Contents

Advertisement

ESIE02–01
3.5
Malfunctioning Electronic Expansion Valve (E9)
E9
Error code
LED indications
The table below shows the LED indications.
Operation
Normal
Malfunction
Error generation
The error is generated when the following coil current condition is not met:
Open circuit < coil current < short circuit.
Resistance values
The table below contains the reference resistance values.
Grey
Black
Yellow
Red
Orange
Causes
The possible causes are:
Part 3 – Troubleshooting
HAP (green)
Grey
40-50 Ω
40-50 Ω
40-50 Ω
40-50 Ω

Malfunctioning electronic expansion valve

Broken or disconnected electronic expansion valve harness
Malfunctioning electronic expansion valve connector connection
Malfunctioning outdoor unit PCB
Outside cause (electric noise...).
H1P (red)
6
6
Black
Yellow
40-50 Ω
40-50 Ω
80-100 Ω
80-100 Ω
80-100 Ω
80-100 Ω
80-100 Ω
80-100 Ω
Error Codes: Outdoor Units
H2P (red)
8
8
8
8
Red
Orange
40-50 Ω
40-50 Ω
80-100 Ω
80-100 Ω
80-100 Ω
80-100 Ω
80-100 Ω
80-100 Ω
1
3 3
4
5
3–43