Reverse Phase - Daikin Sky Air R-407C Service Manual

Sky air r-407c b-series
Table of Contents

Advertisement

ESIE02–01
4.3
Reverse Phase (U1)
U1
Error code
This error code is only for 3-phase equipment.
LED indication
The table below shows the LED indication.
Operation
Normal
Malfunctioning
Error generation
The error is generated when the difference between phase L1 and L3 is not 240˚. The illustration below
shows the 3-phase network.
Causes
The possible causes are:
Part 3 – Troubleshooting
HAP (green)
240˚
L1
90
120
Malfunctioning power supply wiring connection
Broken or disconnected power supply wiring
Malfunctioning outdoor unit PCB
H1P (red)
6
6
L2
L3
180
240
270
360
L1
120˚
L3
L2
240˚
Error Codes: System Malfunctions
H2P (red)
8
8
8
7
1
3 3
4
5
3–55