Daikin Sky Air R-407C Service Manual page 267

Sky air r-407c b-series
Table of Contents

Advertisement

ESIE02–01
The fan is turning
To troubleshoot, proceed as follows:
clockwise
Excessive
To troubleshoot, proceed as follows:
compressor current
Part 3 – Troubleshooting
The fan is turning
clockwise.
Check condensator
connection.
Refer to: fan motor
condensator connection .
Is the
connection
No
correct?
Yes
Replace fan
motor.
The compressor current is
excessive.
Check power
supply
Is there
a suitable
power supply? (Voltage,
lack of phase, etc.)
Yes
Is the current higher
than the setting of the
overcurrent relay?
Yes
Replace
compressor.
Error Codes: Outdoor Units
Correct the connection.
Refer to: fan motor
condensator connection .
Provide suitable
No
power supply.
Replace
No
overcurrent
device.
1
3 3
4
5
3–37