Overview of the heating mode functions
1
Starting and ending
conditions:
RY35-45E(A)Z7V1
2
3
Hot start after
4
defrosting
Used input
5
2–40
Starting conditions
The defrosting starts when all of the following conditions are fulfilled:
The compressor has been running over 40 min
If Ta ≥ 5˚C, outdoor heat exchanger temperature < -3˚C
Outdoor heat exchanger temperature < (Ta x 0,4) - 5˚C.
Ending conditions
The defrosting stops when one of the following conditions is fulfilled:
Defrosting has been running over 10 min, or
Outdoor heat exchanger temperature > 12.5˚C, or
High-pressure switch has been activated, or
Indoor unit has been switched OFF, or
Unit is in another mode than heating.
The hot start function is activated:
40 s after the defrosting ending, or
When Tc > 34˚C (indoor heat exchanger temperature).
The defrost control uses the following inputs:
Input
Outdoor thermistor
Outdoor heat exchanger thermistor
Discharge pipe thermistor
Defrosting start temperature changeover switch
Defrosting forced time changeover switch
Connection on
Connection on
indoor PCB
outdoor PCB
R1T
R2T
R3T
DS1-2
DS2-1
Part 2 – Functional Description