ESIE02–01
5.5
Outdoor unit: Checking the Installation Condition
Checking
To check the installation condition, proceed as follows:
Part 3 – Troubleshooting
Check the space for all air
passage around the suction and
discharge areas.
Is the
minimum space
respected?
Yes
Does the
discharged air from other
outdoor units cause an
increase of the suction
temperature?
Yes
Change the installation
location.
Additional Checks for Troubleshooting
Change the installation
No
location.
Is
the heat
exchanger
clean?
Yes
Is there enough
air flow?
Yes
Check the outdoor ambient
temperature R1T. This temperature
must be lower than 43 °C.
Clean the heat
No
exchanger.
Change the
installation
No
location or
direction.
3–69
1
3 3
4
5