Daikin Sky Air R-407C Service Manual page 254

Sky air r-407c b-series
Table of Contents

Advertisement

Error Codes: Indoor Units
1
Troubleshooting
3
3
4
5
3–24
To troubleshoot, proceed as follows:
Begin
Is the unit a cassette
No
or built-in type?
Yes
Is a drain pump
connected to the
No
indoor unit PCB?
Yes
Does the drain pump
work after restarting
operation?
Yes
Is the drain water
No
level abnormally
high?
Yes
Remove the float switch from
There is a malfunction
X15A, short-circuit X15A, and
of the drain system.
Is the optional drain
No
raising mechanism
connected?
Yes
Connect the
drain pump.
No
Is the float switch
Connect
No
connected to X15A?
float switch
Yes
restart operation.
Does "A3" appear on the
remote controller display?
Yes
Replace indoor
unit PCB.
Is the short-circuit
connector connected to
No
X15A on the indoor
unit PCB?
Yes
Check the continuity of the
short-circuit connector.
Yes
Is there
No
continuity?
Yes
Replace the
indoor unit PCB.
Set to
"emergency" and
check the voltage
of X25A.
No
220-240 VAC?
Yes
Replace the drain
pump.
Replace float
No
switch.
Part 3 – Troubleshooting
ESIE02–01
Connect the
Short-circuit
connector.
Replace the
Short-circuit
connector.
Replace
indoor unit
PCB.