Daikin Sky Air R-407C Service Manual page 286

Sky air r-407c b-series
Table of Contents

Advertisement

Error Codes: System Malfunctions
1
Troubleshooting
3
3
4
5
3–56
To troubleshoot, proceed as follows:
1.
2.
3.
Check power
L1-L2-L3= 400V ±10%
L1-N= 230V ±10%
L2-N= 230V ±10%
L3-N= 230V ±10%
Does the power
correspond with
No
previous data?
Yes
Turn the power off.
Change L1-L2 or L2-L3.
Turn the power on.
Is U1
displayed on the
No
remote controller?
Yes
Replace outdoor
unit PCB.
ESIE02–01
Correct power
supply.
Phases are not
correct.
Part 3 – Troubleshooting