Daikin Sky Air R-407C Service Manual page 266

Sky air r-407c b-series
Table of Contents

Advertisement

Error Codes: Outdoor Units
1
The fan does not
rotate
3
3
4
5
3–36
To troubleshoot, proceed as follows:
The fan does not
Check outdoor
Is the unit a
connector X14 on
outdoor unit PCB.
Try to rotate the
fan with your
you rotate the
fan smoothly?
Check capacitor
the capacitor in
good condition?
1
Check motor windings.
2
Reconnect connector.
rotate.
unit type.
The unit is a
No
R(Y)P71B?
R(Y)P100-125B
Yes
Disconnect
Disconnect
connectors X14A
and X15A on
outdoor unit PCB.
hand.
Can
1
Remove obstacles so the
fan rotates correctly or
No
replace the fan.
2
Reconnect connector.
Yes
Is
1
Replace the capacitor.
No
2
Reconnect connector.
Yes
ESIE02–01