Forced Thermostat Off - Daikin Sky Air R-407C Service Manual

Sky air r-407c b-series
Table of Contents

Advertisement

ESIE02–01
1.8

Forced Thermostat OFF

Applicable units
All indoor units
Purpose
The outdoor unit independently turns its thermostat OFF by means of control other than thermostat
OFF commands from the indoor unit.
Method
The table below contains the different conditions for which the thermostat is turned OFF by the outdoor
unit.
Thermostat OFF
control
Freeze-up function: See page 2–27.
Cooling overload
Only for
R(Y)P71-250B
Heating overload
(peak cut-off)
Discharge pipe
high temperature
Only for
R(Y)P71-250B
Td disconnection
Only for
R(Y)P71-250B
Used input
The forced thermostat OFF control uses the following inputs:
Input
Outdoor heat exchanger thermistor
Indoor heat exchanger thermistor
Discharge pipe thermistor
Part 2 – Functional Description
Indicator
Starting conditions
Outdoor heat
Tc > 63˚C for 90 s contin-
exchanger
uously
temperature Tc
(min. 60 - max. 66˚C for
practice function)
Indoor heat
Tc > 62.5˚C for 30 s con-
exchanger
tinuously
temperature Tc
(min. 59.5 - max. 65.5˚C
for practice function)
Discharge pipe
Td > 125˚C for 20 s con-
temperature T2
tinuously
Discharge pipe
Td is determined to be
thermistor T2
disconnected from the
piping 5 min after the
compressor starts.
Td < 55˚C
Td < Ta + 10˚C
Td ≤ 5 K
General Functionality
Result
Reset
The thermo-
stat is
turned OFF.
Next start,
initial open-
ing E.V.:
+ 70 pulses
(cooling)
Remocon
+ 80 pulses
OFF
(heating)
Retry 6 x
until
final error
"F3"
Connection on
Connection on
indoor PCB
outdoor PCB
R2T
R2T
R3T
1
2
3
4
5
2–13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents