Malfunctioning Drain System - Daikin Sky Air R-407C Service Manual

Sky air r-407c b-series
Table of Contents

Advertisement

ESIE02–01
2.5
Malfunctioning Drain System (AF)
AF
Error code
LED indications
The table below shows the LED indications.
Operation
Normal
Malfunctioning
Error generation
The error is generated when the float switch changes from ON to OFF while the compressor is OFF.
Causes
The possible causes are:
Troubleshooting
To troubleshoot, proceed as follows:
∗In FHY and FAY problems can also
occur in the optional drain-up kit.
Part 3 – Troubleshooting
Error in the drain pipe installation
Malfunctioning float switch
Malfunctioning indoor unit PCB.
Are float
NO
switch and drain pipe
normal?
YES
Is drain-up
kit installed?
YES
Is drain pump
normal?
YES
Is
amount
of circulated drain
water excessive after
pump stops
operation?
YES
Does
drain water
flow in reverse during
non-operation?
YES
HAP (green)
6
6
Is water
NO
drainage system
normal?
YES
NO
NO
NO
NO
Error Codes: Indoor Units
HBP (green)
6
6
Possible failure of float switch.
Check to see if drain-up height
and horizontal pipe length
exceed specifications.
Clogged drain water discharge
system
Clogged drain pump
Faulty float switch
Replace indoor unit PCB.
Check to see if drain-up height
and horizontal pipe length
exceed specifications.
Check jumper connector
X15A.
Check drain pump and drain
pipe.
Check water drainage system.
Check to see if drain-up height
and horizontal pipe length
exceed specifications.
Faulty trap in water drainage
system
Replace indoor unit PCB.
3–27