Outdoor Unit Identification Function - Daikin Sky Air R-407C Service Manual

Sky air r-407c b-series
Table of Contents

Advertisement

Overview of the heating mode functions
3.5

Outdoor Unit Identification Function

1
Applicable units
2
3
Purpose
Operating modes
4
5
Used input
2–44
The outdoor unit identification function is applicable for the following units:
Model type
Model name
Cassette
FHYCP and FUYP
Corner
FHYKP
Ceiling
FUYP
Wall
FAYP
Duct
FDYP and FHYBP
The purpose of the outdoor unit identification function is to enable the indoor unit to automatically
determine which operating mode has to be set in function of the outdoor unit type (c/o or h/p).
The possible operating modes are:
Outdoor unit
Operating modes
h/p
Fan
Cooling
Dry keep
Heating
c/o
Fan
Cooling
Dry keep
The outdoor unit identification function uses the following inputs:
Input
Indoor PCB
Outdoor PCB
TC: Transmission circuit
RC: Receiving circuit
Connection on
Connection on
indoor PCB
outdoor PCB
TC & RC
TC &RC
Part 2 – Functional Description