End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
Temperature Input Calibration
The following five (5) Offset screens are used only if calibration of a sensor designated
to perform the listed function is necessary.
Example: If the temperature sensor for Morning Warm Up (MWU) is checked and a
difference between the actual measured room temperature and the corresponding
measured sensor value is found, by programming the amount of error into the
Temperature Input Offset for Morning Warm Up (MWU) Heat — The sensor can be
calibrated.
Calibration and Offset Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will bypass this section.
Temperature Calibration Offset For
RTM Zone Temperature Input
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Temperature Calibration Offset For
RTM Aux Temperature Input
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Temperature Calibration Offset For
RTM Outside Air Temperature Input
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
RT-SVP04F-EN
0.0 F
0.0 F
0.0 F
System Programming SETUP
Used with: All Units
Used With: All Units
Factory Presets: 0.0 F
Possible Values: Plus or Minus 5.0
F
Used With: All Units
Factory Presets: 0.0 F
Possible Values: Plus or Minus 5.0
F
Used With: All Units
Factory Presets: 0.0 F
Possible Values: Plus or Minus 5.0
F
79