Sump Water Heater Setpoint:
Low Sump Temp Activates Heater Output
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed (if
applicable)
Cond Temp Control Band
Lower Limit:
80 F
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
Cond Temp Control Band
Temporary Low Limit Suppression:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Cond Temp
Efficiency Check Point:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Cond Temp
Low Ambient Control Point:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
RT-SVP04F-EN
38°F
Upper Limit: 120 F
10 F
105 F
90 F
System Programming SETUP
Used With: All IntelliPak II units
with water-cooled condensers and
sump heat installed.
Factory Preset: 38 F
Possible Values: 38-43 F
Used With: All Rooftop Units and
Air handlers when DX Cooling is
installed.
Factory Presets: Upper: 120 F,
Lower: 80 F
Possible Values: Lower: 70 F to 90
F, Upper: 110 F to 130 F
Used With: All Rooftop Units and
Air handlers when DX Cooling is
installed.
Factory Presets: 10 F
Possible Values: 0 to 20 F
Used With: All Rooftop Units and
Air handlers when DX Cooling is
installed.
Factory Presets: 105 F
Possible Values: 95 to 115 F
Used With: All Rooftop Units and
Air handlers when DX Cooling and
low ambient dampers are installed.
Factory Presets: 90 F
Possible Values: 80 F to 100 F
Note: All low ambient dampers
control to this condensing
temperature
61