Trane IntelliPak I Programming, Troubleshooting Manual page 111

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

Sump Fill Relay:
Sump Drain Relay:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Sump Heater Relay:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed
(if applicable).
Condenser Fan Outputs (MCM 1)
K1 OFF
K2 OFF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
Note: If either 1A or 1B (Ckt 1) is set to AUTO, the other will
automatically be changed to AUTO. The same is true of 2A
and 2B (Ckt 2). If either is set to AUTO, the other will be
changed also
Condenser Fan Speed (MCM)
Ckt 1 0%
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed
(if applicable).
RT-SVP04F-EN
OFF
OFF
OFF
K5 OFF
K6 OFF
Ckt 2 0%
System Testing & Troubleshooting
Used With: All IntelliPak II units
with water-cooled condensers
installed
Factory Preset: OFF
Possible Values: ON, OFF
Used With: All IntelliPak II units
with water-cooled condensers and
sump heat installed
Factory Preset: OFF
Possible Values: ON, OFF
Used With: All Rooftops or Air
Handlers with DX Cooling and
Airside Condensers.
Possible Values: ON, OFF, AUTO
Used With: All Rooftops and Air
Handlers with DX Cooling and
Airside Condensers.
Possible Values: AUTO, 0-100%
(default 0%)
111