Trane IntelliPak I Programming, Troubleshooting Manual page 57

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

Evap Temperature Limit. Shut Off Circuit
if (Leaving - Entering) Exceeds: 35ºF
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
Note: On units with Dehumidification installed a non-adjustable
Evap Temperature Limit of 40 F is used for the Reheat Circuit
only.
Coil Frost Cutout Temperature. Shut off
Compressors If Evap Temp Is Below:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
VAV Control Functions Submenu
Press ENTER to Review or Adjust
1. Press the NEXT key until the following screen is displayed.
Supply Air Temp Reset Type:
Cooling: NONE
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Supply Air Temp Reset type:
Cooling:
NONE
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable)
RT-SVP04F-EN
30 F
Heating:
NONE
System Programming SETUP
Used With: All Units
Factory Preset: 35º F
Possible Values: 25-40º F
Used With: All Rooftop Units and
Air Handlers when DX Cooling is
installed
Factory Preset: 30 F
Possible Values: 25 F to 35 F
Used With: All Units
Used With: Rooftops and Air
Handlers when no cooling is installed
Possible Values: Cool: NONE,
ZONE, OA
Used With: All Units when
Hydronic, Electric, or Modulating
Gas Heat installed
Possible Values: Cool/Heat: NONE,
ZONE, OA
57

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Intellipak ii

Table of Contents