Dehumidification Status; Humidification Status - Trane IntelliPak I Programming, Troubleshooting Manual

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

System Operating Status

Dehumidification Status:

by Comfort Control Override is Active
1. Pressing the NEXT key will scroll forward through the screens.
2. Pressing the PREVIOUS key will scroll backwards to view the
previously displayed screen.
3. Press the NEXT key until the following screen is displayed.
(if applicable)
by Call for Cooling Demand Limit
by Compressor Lockout Sources
by Occ Dehumid Function Disable
by Dehumid Override Zone Temp High
by OA Temperature Out Of Range
by Unocc Dehumid Function Disable
by Comfort Control Override is Active
by Required Sensor Failure Condition
by Insufficient Airflow Condition
by Sat Reheat Cond Temp Sensor Fail
By Reheat Head Pressure High Limit
(Blank)
Condenser Coil Purge is Active
Humidification
Status:
Key Stroke Operation (1)
1. by Occ Humidification Function Disable
2. by Unocc Humidification Function Disable
3. Humidification is Inactive
4. Humidification is Active
1. Press the NEXT key until the following screen is displayed. (If
applicable)
End of Submenu (NEXT) to Enter STATUS
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.
28
DISABLED
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "DISABLED"
If 1st line is "ENABLED"
If 1st line is "ENABLED"
Humidification is
ENABLED
Active
Used With: All IntelliPak with
Dehumidification option installed.
Top Line Possible Values:
ENABLED, DISABLED
Bottom line Possible Values: See
below
Used With: Used With: All units
with Humidification option installed.
Possible Values: ENABLED,
DISABLED
by Occ Humidification Function
Disable (If 1st line is "DISABLED"),
by Unocc Humidification Function
Disable (If 1st line is "DISABLED"),
Humidification is Inactive (If 1st line
is "ENABLED" and output is de-
energized, Humidification is Active
(If 1st line is "ENABLED" and output
is energized)