Morning Warmup Function:
Morning Warmup Type:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
Supply Air Tempering Function:
Warm Up Outside Air Used For Ventilation
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Unocc Mech Cooling Function:
Unocc Mech Cooling Function:
Unocc Heating Function:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
Occupied Dehumid Function:
Unoccupied Dehumid Function:
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 for the next value.
5. Press the NEXT key until the following screen is displayed (if
applicable).
RT-SVP04F-EN
ENABLED
FULL CAPACITY
ENABLED
ENABLED
OR
ENABLED
ENABLED
ENABLED
ENABLED
System Programming SETUP
Used With: All Units when Gas,
Electric, or Hydronic Heat is
installed.
Factory Presets: Function:
ENABLED, MWU Type: Full
Capacity
Possible Values: Function:
ENABLED, DISABLED
MWU Type: FULL CAPACITY,
CYCLING CAPCITY
Used With: All Units when
Modulating Gas, Electric or Hydronic
Heat is installed
Factory Preset: ENABLED
Note: Possible Values: ENABLED,
DISABLED* (Note: Supply
Air Tempering is not used
with staged gas heat)
Used With: All Rooftop Units and
Air Handler Units when DX Cooling is
installed or Air Handler with chilled
water installed.
Factory Preset: ENABLED
Possible Values: Cooling:
ENABLED, DISABLED
Used With: All Units when Gas,
Electric, Hydronic, or External Heat
is installed
Factory Presets: Cooling &
Heating: ENABLED
Possible Values:
Cooling &
Heating: ENABLED, DISABLED
Used With: All units with
Dehumidification installed.
Possible Values: ENABLED,
DISABLED
55