Trane IntelliPak I Programming, Troubleshooting Manual page 87

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

Actuator Setup
Max Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Direct/Reverse Act
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Stroke Time
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Min Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Voltage
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Direct/Reverse Act
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
Actuator Setup
Max Stroke Time
1. Press the + or - key until the proper value is displayed.
2. Press the ENTER key to confirm this choice.
3. Press the NEXT key until the following screen is displayed.
RT-SVP04F-EN
Modulating Gas Heat
10 VDC
Modulating Gas Heat
DIRECT ACTING
Exh Bypass Damper
60 Sec
Exh Bypass Damper
2.0 VDC
Exh Bypass Damper
10.0 VDC
Exh Bypass Damper
DIRECT ACTING
OA Bypass Damper
60 Sec
System Programming SETUP
Used With: All Rooftop Units and
Air Handlers when Modulating Gas is
installed
Factory Presets: 10 VDC
Possible Values: 0.1 to 10.0 Volts
VDC
Used With: All Rooftop Units and
Air Handlers Modulating Gas is
installed
Factory Presets: Direct Acting
Possible Values: Direct Acting,
Reverse Acting
Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 60 seconds
Possible Values: 1-255 seconds
Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 2.0.0 VDC
Possible Values: 0.0 - 10.0 VDC
Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 10.0.0 VDC
Possible Values: 0.0 - 10.0 VDC
Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: DIRECT
Possible Values: DIRECT, REVERSE
Used With: All IntelliPak II units
with Energy Recovery installed.
Factory Preset: 60 seconds
Possible Values: 1-255 seconds
87