Controlling Sensor Status Submenu Screens - Trane IntelliPak I Programming, Troubleshooting Manual

Commercial single zone rooftop air conditioner with variable air volume (vav) controls
Table of Contents

Advertisement

System Operating Status
Active Space Pressure SETPOINT From
HI (KEYPAD) SETPOINT MENU
1. Press the NEXT key until the following screen is displayed. (if applicable)
Active Space Pressure Deadband
1. Press the NEXT key until the following screen is displayed.
End of Submenu (NEXT) to Enter SETUP Status
1. Press the NEXT key to leave the submenu and show following
screen.
2. Press PREVIOUS to page back through the submenu.

CONTROLLING SENSOR STATUS SUBMENU SCREENS

Controlling Sensor Status Submenu
Press ENTER to View Data in This Submenu
1. Pressing the NEXT key will bypass this section.
Active Supply Air Temp Sensor Input From
SUPPLY AIR
1. Press the NEXT key until the following screen is displayed.
Active Daytime WU Temp Sensor Input From
RTM ZONE TEMP INPUT
1. Press the NEXT key until the following screen is displayed.(if
applicable)
Active Unocc Zone Temp Sensor Input From
RTM ZONE TEMP INPUT
1. Press the NEXT key until the following screen is displayed. (if
applicable)
44
is
0.08 IWC
0.10 IWC
is
50.0 F
is
82.0 F
is
75.0 F
Used With:
All Units when Power
Exhaust with Statitrac is installed or
Return Fan with Statitrac installed
Possible Values: HI (Keypad)
SETPOINT Menu, GBAS 0-5 VDC
Module, BAS/Network, GBAS 0-10
VDC Module; SETPOINT range: -0.2
to 0.30 IWC
Used With:
All Units when Power
Exhaust with Statitrac is installed or
Return Fan with Statitrac Installed
Possible Values: HI (KEYPAD)
SETPOINT MENU, SETPOINT range:
0.02 to 0.20 IWC
Used With: All Units
Used With: All Units
Possible Values: RTM Supply Air
Temp Input, BAS/Network
Used With: All units when Gas,
Electric, Hydronic or External Heat is
installed and DWU is enabled
Possible Values: RTM Zone Temp
Input, NSB Panel Temp Sensor
Input, RTM Aux Temp Input, Heat
Module Aux Temp Input, ECEM
Return Air Temp Input, BAS/Network
Sensor range: -40 F to 200 F
Used With: All Units
Possible Values: RTM Zone Temp
Input, NSB Panel Temp Sensor
Input, RTM Aux Temp Input, Heat
Module Aux Temp Input, ECEM
Return Air Temp Input, BAS/
Network, Sensor range: -40 F to
200 F
RT-SVP04F-EN